Marvair AVP 24 Manuel Page 22

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 38
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 21
22
ComPac 6/09-18
2.5 Fresh Air Hood Installation (AVP24-30-36)
1. Cut and remove insulation on the inside of the lower front access panel in the shape of the rectan-
gular opening. See Figure 6.
2. Insert ange on hood into opening and secure using the two #8 x 1/2 sheet metal screws
supplied.
Figure 6. Fresh Air Hood Installation
Table 6. Maximum Static Pressure
(For units with 2" Pleated Filters)
BASIC MODEL MAXIMUM TOTAL STATIC MINIMUM FILTER AREA
24 .30 2.25 sq. ft.
30/36 .40 3.00 sq. ft.
42/48/60/72 .50 3.90 sq. ft.
2.6 Bracket Installation (AVP24-72)
1. Models AVP24-72 have built-in mounting anges.
2. Apply a bead of silicone sealer on the wall side of the bottom support brackets on the unit. Circle
the mounting holes with the silicone bead.
3. Refer to Figure 7. Attach the bottom support bracket to the wall using appropriate 3/8" diameter
hardware.
For example, on wooden structures, use 3/8" x 2-1/2" all-thread lag screws. The screws must penetrate
the center of the wall stud. Drill a pilot hole in the stud to prevent it from splitting.
Vue de la page 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 37 38

Commentaires sur ces manuels

Pas de commentaire