3.1 CheCk-ouT of CoolinG CyCle
Important: Be sure that the crankcase heater (if used) has been energized for at least 24 hours
before starting the unit(s). Double-check all electrical connections before applying power.
ComPac
®
air conditioners with scroll compressors running on power must be checked for
proper rotation during the initial start-up. Please refer to Section 2.8 for determining if the
compressors are rotating correctly. Incorrect rotation can damage the compressor and is not
covered by the warranty
Procedure:
1. Set the cooling temperature on the wall thermostat to a point higher than the ambient temperature.
Set the heating temperature to a temperature that is lower than the ambient.
2. Set the thermostat system switch in the AUTO position. Nothing should operate at this time.
3. Set the time delay in the ComPac
®
I or ComPac
®
II A/C control box to three minutes. Check the
changeover setting of the H205A or dry bulb sensor and reset it if needed (ComPac II A/C only).
See Section 1.6.
4. Slowly lower the thermostat's cooling temperature until the switch closes. The indoor fan should
operate.
Once the indoor fan turns on, allow approximately three minutes for the compressor to start. Note that
the outdoor fan may not come on immediately, because it is cycled by refrigerant pressures.
NOTE: (ComPac
®
II A/C only) To check the system operation under different ambient conditions, the
air temperature and enthalpy sensors must be "tricked". When outdoor ambient conditions are higher
than the control setting, a component cooler aerosol may be sprayed directly into the enthalpy sensor
to simulate low enthalpy conditions, causing the economizer damper to open.
Alternately, when outdoor conditions are lower than the set point, a source of heat such as a hair dryer
can be directed on the air temperature sensor to simulate warmer conditions, which will bring on
mechanical cooling and start the compressor.
5. To stop cooling, slowly raise the thermostat cooling to a temperature higher than the ambient.
If the unit fails to operate, refer to the troubleshooting information in Chapter 4.
Follow the same procedure for additional units.
NOTE: The fan purge allows the indoor fan to run for approximately 90 seconds after the compressor
is off. This operation provides a small improvement in system S.E.E.R.
3.2 CheCk-ouT of heaTinG CyCle
Procedure: (Applies only to units with resistance elements)
1. Raise the heating temperature to a setting which is higher than the ambient temperature. The fan
and electric heat should immediately cycle on.
2. Move the system switch to the "OFF" position. All functions should stop.
NOTE: (ComPac
®
II A/C only) The damper blade should remain closed during the heating cycle (un-
less the minimum position potentiometer has been set for constant ventilation A fully counterclockwise
position corresponds to full closure of the damper.