Marvair AVP 24 Manuel Page 12

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 38
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 11
12
ComPac 6/09-18
1.7 opTional ConTrols & paCkaGes
Hard Start Kit
Used on single phase equipment to give the compressor higher starting torque under low voltage condi-
tions. Generally not recommended on units with scroll compressors.
Extreme Duty Package
The Extreme Duty Package allows selected Marvair
®
ComPac
®
I & ComPac
®
II air conditioners to
operate in extremely cold and hot ambient conditions. The Extreme Duty Kit is always factory installed
and is available on all ComPac
®
air conditioners. ComPac
®
I air conditioners (non-economizer units)
will operate from 0° F to 130° F (-18° to 54°C). ComPac
®
II air conditioners (economizer units) will
operate from -20° F to 130° F (-29° to 54°C).
The Extreme Duty Package includes a suction line accumulator, thermal expansion valve (TXV),
crankcase heater, hard start kit, an auto reset, adjustable high pressure switch and an outdoor thermostat
and fan cycle switch. The fan cycle control is standard on all ComPac
®
air conditioners and operates
based upon the liquid line pressure. The outside thermostat closes whenever the outside temperature is
below 50°F (10°C) and opens when the outside temperature is 50° F (10°C) or higher. Whenever the
temperature is below 50°F (10°C), the fan cycle switch is in the circuit; when temperatures are 50° F
(10°C) or higher, the fan cycle switch is not in the circuit. The fan cycle control is used with a TXV to
prevent excessive cycling or "hunting" of the TXV.
Coastal Environmental (ComPac® I A/C Only)
Recommended for units to be installed near an ocean or on seacoast. Includes corrosion resistant
fasteners, sealed condenser fan motor, protective coating applied to all exposed internal copper in the
condenser section and a protective coating on the condenser coil.
Stainless Steel Cabinet (ComPac® I A/C Only)
All sheet metal constructed of stainless steel.
Hot Gas Bypass (ComPac® I A/C Only)
Used in specialty applications; i.e., Magnetic Resonance Imaging (MRI) buildings, to prevent magnetic
voltage disturbance caused by compressor cycling. Two hot gas bypass option packages are available
to allow operation to 20°F (-7°C) or minus 20°F (-29°C). Please refer to Hot Gas Bypass Application
Bulletin for details.
Electric Reheat Dehumidication
A humidity controller (p/n 50057) allows electric heat and cooling to operate simultaneously. Marvair
®
air conditioners equipped with the dehumidication option allow the indoor humidity of the controlled
environment to be maintained at or below a certain humidity set point. These units do not have the
ability to add humidity to the building.
IMPORTANT: The electrical wire and breaker or fuses must be sized for simultaneous operation
of the electric heater and the air conditioner. Refer to the data sticker on the unit or the ComPac
®
Air Conditioner Product Data Sheet for the sizing information.
Dehumidication is achieved by operating mechanical cooling in conjunction with electric reheat. The
strip heat is sized approximately to the sensible capacity of the total tonnage of the machine (i.e., on a
24,000 BTU unit the strip heat is sized at approximately 20,000 BTU). Because the strip heat is sized
to the approximate sensible cooling capacity, only selected models are available.
Operation:
When the humidity rises above the set point on the humidity controller both mechanical cooling and
Vue de la page 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 37 38

Commentaires sur ces manuels

Pas de commentaire