AVPA & HVEA PDS 4/2012 rev.3 12
Summary Ratings (Wire Sizing) -
HVEA Air Conditioner with Reheat (“R”) and
Single Stage Compressor
Manual Damper (“N”) or Economizer (“C”)
ELECT. HEAT 050 = 5 kw 060 = 6 kw 090 = 9 kw
120 = 12 kw
(8 kw Reheat on 1ø models)
150 = 15 kw
(10 kw Reheat on 1ø models)
BASIC
MODEL
VOLTAGE
PHASE
CKT #1 CKT #1 CKT #1 CKT #1 CKT #2 CKT #1 CKT #2
MCA
1
MFS
2
MCA
1
MFS
2
MCA
1
MFS
2
MCA
1
MFS
2
MCA
1
MFS
2
MCA
1
MFS
2
MCA
1
MFS
2
HVEA24ACA 208-230/1 46.6 50
HVEA30ACA 208-230/1 52.9 60
HVEA36ACA 208-230/1 26.4 40 41.6 45
HVEA42ACA 208-230/1 30.4 50 52.1 60
HVEA49ACA 208-230/1 34.4 50 52.1 60
HVEA60ACA 208-230/1 40.1 60 52.1 60
HVEA24ACC 208-230/3 32.2 35
HVEA30ACC 208-230/3 34.0 35
HVEA36ACC 208-230/3 36.6 40
HVEA42ACC 208-230/3 49.7 50
HVEA49ACC 208-230/3 51.4 60
HVEA60ACC 208-230/3 27.0 40 36.1 40
HVEA24ACD 460/3 16.3 20
HVEA30ACD 460/3 18.2 20
HVEA36ACD 460/3 19.1 20
HVEA42ACD 460/3 23.9 25
HVEA49ACD 460/3 24.8 25
HVEA60ACD 460/3 31.2 35
1
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
2
MFS = Maximum Fuse Size
The 460 volt ACD models are calculated at 460 volts. All 460 units will have a step down transformer for the 230 volts motors. This chart should only be used as a guideline for
estimating conductor size and overcurrent protection.
For the requirements of specic units, always refer to the data label on the unit.
Unit Load Amps -
HVEA Air Conditioner with Single Stage Compressor
BASIC
MODEL
NUMBER
VOLTAGE
PHASE
HERTZ
CURRENT
AMPS
LOAD OF RESISTIVE ELEMENTS HEATING
ELEMENTS ONLY (AMPS)
TOTAL MAXIMUM HEATING AMPS (STANDARD UNIT)
AC
1
IBM
2
04
kW
05
kW
06
kW
08
kW
09
kW
10
kW
12
kW
15
kW
04
Kw
05
Kw
06
Kw
08
Kw
09
Kw
10
Kw
12
Kw
15
Kw
HVEA24ACA 208-230/1/60 17.4 2.8 16.7 20.8 25.0 33.3 41.7 19.5 23.6 27.8 36.1 44.5
HVEA30ACA 208-230/1/60 18.4 2.8 16.7 20.8 25.0 33.3 41.7 50.0 62.5 19.5 23.6 27.8 36.1 44.5 52.8 65.3
HVEA36ACA 208-230/1/60 22.2 2.8 16.7 20.8 25.0 33.3 41.7 50.0 62.5 19.5 23.6 27.8 36.1 44.5 52.8 65.3
HVEA42ACA 208-230/1/60 25.4 2.8 20.8 41.7 50.0 62.5 23.6 44.5 52.8 65.3
HVEA49ACA 208-230/1/60 28.9 4.3 20.8 41.7 50.0 62.5 25.1 46.0 54.3 66.8
HVEA60ACA 208-230/1/60 33.5 4.3 20.8 41.7 50.0 62.5 25.1 46.0 54.3 66.8
HVEA24ACC 208-230/3/60 12.3 2.8 14.4 21.7 28.9 36.1 17.2 24.5 31.7 38.9
HVEA30ACC 208-230/3/60 13.9 2.8 14.4 21.7 28.9 36.1 17.2 24.5 31.7 38.9
HVEA36ACC 208-230/3/60 16.0 2.8 14.4 21.7 28.9 36.1 17.2 24.5 31.7 38.9
HVEA42ACC 208-230/3/60 19.2 2.8 14.4 21.7 28.9 36.1 17.2 24.5 31.7 38.9
HVEA49ACC 208-230/3/60 20.8 4.3 14.4 21.7 28.9 36.1 18.7 26.0 33.2 40.4
HVEA60ACC 208-230/3/60 23.0 4.3 14.4 21.7 28.9 36.1 18.7 26.0 33.2 40.4
HVEA24ACD 460/3/60 6.3 1.4 7.2 10.8 14.4 18.0 8.6 12.2 15.8 19.4
HVEA30ACD 460/3/60 7.9 1.4 7.2 10.8 14.4 18.0 8.6 12.2 15.8 19.4
HVEA36ACD 460/3/60 8.6 1.4 7.2 10.8 14.4 18.0 8.6 12.2 15.8 19.4
HVEA42ACD 460/3/60 8.9 1.4 7.2 10.8 14.4 18.0 8.6 12.2 15.8 19.4
HVEA49ACD 460/3/60 9.8 2.2 7.2 10.8 14.4 18.0 9.4 13.0 16.6 20.2
HVEA60ACD 460/3/60 11.3 2.2 7.2 10.8 14.4 18.0 9.4 13.0 16.6 20.2
1
AC = Air Conditioner (Includes Indoor Blower Motor amps)
2
IBM = Indoor Blower Motor
Heating kW rated at 240v. for 208-230v. units (A & C models). Derate heat by 25% for operation on 208v. Heating kW rated at 480v. for 460v. units (D models). Total heating
amps for all 1ø units with 15 kW of heat includes both circuits (#1 & #2). Note: 3ø units contain 1ø motor loads. Values shown are maximum phase loads. Loads are not equally
balanced on each phase. Total maximum heating and cooling amps include motor loads.