Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS, 1/2011
12
Unit Load Amps (Heating) -
AVPA Heat Pumps with GreenWheel
®
ERV -
Ventilation Configuration (“H”)
MODEL
NUMBER
VOLTAGE
PHASE
HERTZ
CURRENT (AMPS)
LOAD OF RESISTIVE HEATING ELEMENTS
(AMPS)
TOTAL MAXIMUM HEATING LOAD (AMPS)
HEAT PUMP
INCLUDES IBM
1
INDOOR
BLOWER
GREENWHEEL
ERV
04
kW
05
kW
06
kW
08
kW
09
kW
10
kW
12
kW
15
kW
04
Kw
05
Kw
06
Kw
08
Kw
09
Kw
10
Kw
12
Kw
15
Kw
AVPA24HPA 208-230/1/60 15.7 1.5 2.2 16.7 20.8 25.0 33.3 n/a 41.7 n/a n/a 34.6 38.7 42.9 51.2 n/a 59.6 n/a n/a
AVPA30HPA 208-230/1/60 18.4 2.5 2.2 n/a 20.8 25.0 n/a n/a 41.7 50.0 62.5 n/a 41.4 45.6 n/a n/a 62.3 53.9 62.3
AVPA36HPA 208-230/1/60 22.2 2.5 2.2 n/a 20.8 25.0 n/a n/a 41.7 50.0 62.5 n/a 45.2 49.4 n/a n/a 66.1 57.7 66.1
AVPA42HPA 208-230/1/60 25.7 4.3 2.2 n/a 20.8 n/a 33.3 n/a 41.7 50.0 62.5 n/a 48.7 n/a 61.2 n/a 69.6 61.2 69.6
AVPA49HPA 208-230/1/60 27.7 4.3 2.2 n/a 20.8 n/a n/a n/a 41.7 50.0 62.5 n/a 50.7 n/a n/a n/a 71.6 63.2 71.6
AVPA60HPA 208-230/1/60 34.2 4.3 2.2 n/a 20.8 n/a n/a n/a 41.7 50.0 62.5 n/a 57.2 n/a n/a n/a 78.1 69.7 78.1
AVPA24HPC 208-230/3/60 11.2 1.5 2.2 n/a n/a 14.4 n/a 21.7 n/a 28.9 36.1 n/a n/a 27.8 n/a 35.1 n/a 42.3 49.5
AVPA30HPC 208-230/3/60 13.3 2.5 2.2 n/a n/a 14.4 n/a 21.7 n/a 28.9 36.1 n/a n/a 29.9 n/a 37.2 n/a 44.4 51.6
AVPA36HPC 208-230/3/60 17.5 2.5 2.2 n/a n/a 14.4 n/a 21.7 n/a 28.9 36.1 n/a n/a 34.1 n/a 41.4 n/a 48.6 55.8
AVPA42HPC 208-230/3/60 19.5 4.3 2.2 n/a n/a 14.4 n/a 21.7 n/a 28.9 36.1 n/a n/a 36.1 n/a 43.4 n/a 50.6 57.8
AVPA49HPC 208-230/3/60 19.6 4.3 2.2 n/a n/a 14.4 n/a 21.7 n/a 28.9 36.1 n/a n/a 36.2 n/a 43.5 n/a 50.7 57.9
AVPA60HPC 208-230/3/60 23.6 4.3 2.2 n/a n/a 14.4 n/a 21.7 n/a 28.9 36.1 n/a n/a 40.2 n/a 47.5 n/a 54.7 61.9
AVPA24HPD 460/3/60 6.6 0.8 1.1 n/a n/a 7.2 n/a 10.8 n/a 14.4 18.0 n/a n/a 14.9 n/a 18.5 n/a 22.1 25.7
AVPA30HPD 460/3/60 7.8 1.3 1.1 n/a n/a 7.2 n/a 10.8 n/a 14.4 18.0 n/a n/a 16.1 n/a 19.7 n/a 23.3 26.9
AVPA36HPD 460/3/60 8.2 1.3 1.1 n/a n/a 7.2 n/a 10.8 n/a 14.4 18.0 n/a n/a 16.5 n/a 20.1 n/a 23.7 27.3
AVPA42HPD 460/3/60 7.1 2.2 1.1 n/a n/a 7.2 n/a 10.8 n/a 14.4 18.0 n/a n/a 15.4 n/a 19.0 n/a 22.6 26.2
AVPA49HPD 460/3/60 7.2 2.2 1.1 n/a n/a 7.2 n/a 10.8 n/a 14.4 18.0 n/a n/a 15.5 n/a 19.1 n/a 22.7 26.3
AVPA60HPD 460/3/60 11.7 2.2 1.1 n/a n/a 7.2 n/a 10.8 n/a 14.4 18.0 n/a n/a 20.0 n/a 23.6 n/a 27.2 30.8
Heating kW is rated at 240 volts on the HPA & HPC models. Derate heater output by 25% for operation at 208 volts. Total heating amps for single phase units with two circuits (#1 and #2) includes
both circuits. Heating kW is rated at 480 volts on the HPD models. Three phase models contain single phase motor loads.
Total heating and cooling amps includes all motors. Values shown are maximum phase loads. Loads are not equally balanced on each phase.
1
IBM-Indoor Blower Motor